Installation cable fire-resistant ALSECURE PREMIUM 300/500 V, NexansArt. no.: 0474110
ALSECURE® PREMIUM is a halogen free, fireproof, unshielded installation cable. The cable is intended for fixed installation on ladders, directly on the wall and in pipes or ducts. Used when there is a requirement for functionality during and after a fire in, for example, emergency lighting, fire alarm system and control system.
ALSECURE® PREMIUM cables are designed for use in security systems (emergency lighting, fire alarm systems, etc) in all public areas, such as concert halls, theatres, cinemas, shops, hospitals, schools, high-rise buildings, tunnels and industries. ALSECURE® PREMIUM cables, are fireproof and flame retardant, have low smoke development and are halogen-free. If a fire occurs, the flue gases are low- corrosive.
ALSECURE® PREMIUM cables must be installed in accordance with applicable regulations and standards, and must be protected against direct sunlight during outdoor installation.
When installing between 0 ° C and -10 ° C, the cable must be heated at least 48 hours before installation. ALSECURE® PREMIUM is not suitable for placing in ground.
Fire classes: Fire resistant in accordance with NF C 32-070 Cat. CR1, IEC 60331, EN 50200, EN 1363, NBN C 30-004 FR2 Rf2h. Flame spread class according to NF C 32-070 Cat. C1 & C2, IEC 60332 Part 2 & 1, EN 50266, NBN C 30-004 F2. Low smoke development: NF C 32-073, IEC 61034, EN 50268. Halogen-free : NF C 32-074, IEC 60754, EN 50267. Smoke gases : NF C 32-074, IEC 60754, EN 50267. Low-corrosive : NF C 32-074, IEC 60754, EN 50267
Design: Wire: copper. Insulation: halogen-free thermoplastic INFIT™ technology. Outer jacket: HFFR (polyolefin without halogens).