Produkten är miljöbedömd av SundaHus
ETL-10 is a self-regulating heating cable for the freeze protection of pipes, 10W/m. The outer jacket is PVC-free. The installation is simple and the heating cable can be installed both on and inside water pipes. Max installation length: 60 m internally, 100 m externally. ETL-10 is supplied in running metres on a drum, up to 305 m, and can be cut to the exact desired length. Thereafter a connection and termination kit is fitted. The heating cable can also be crossed without any risk of overheating.

ETL-10 is intended for permanent installation with thermostat T2TraceTemp, earth fault breaker and an external sensor. Energy savings can be up to 80% compared with an installation without a thermostat.

For internal installation, the installation is complemented with a T or Y connector. For a T-connector, a waterproof lead through is also required. This is, however, included in the Y-connector. Complement with an earth fault breaker. ETL-10 is the only heating cable available in the market which is S-marked and food-grade approved by SITAC for internal installation in drinking water pipes. It does not release any substances or odd tastes
  • Article number: 
    8946000
  • Suppl. article no: 
    924269-000
  • Ean no: 
    7330957002585
  • Replaces art.nbr: 
    8946015 8946022 8946025
  • Material class 
    QX5201
Technical data
  • Packagin Size: 1 M/305 M/1220 M/7320 M
  • Type: R-ETL-10
  • Application: Other
  • Cable type: Single core
  • Heating capacity: 10 W/m
  • Width: 5.8 mm
  • Height: 8.5 mm
  • Nominal voltage: 230 V
  • Max. hold temperature: 65 °C
  • Colour: Black
  • Screening: Braiding
  • REACH Date: 2021-11-22
  • REACH Information obligation: No
  • Max connection length: Inside 60m, outside 100m.
  • Information: Power: 10 W/m at +5°C on metal pipe
    Earth fault breaker: 30mA